FORTRON CHAMP 6K TOWER ONLINE
- 2,316.94лв. | €1,184.63
Manufacturer | FORTRON | |
Capacity | 6000 VA / 5400 W | |
Input | Low Line Loss: 110 VAC ± 3 % at 50% Load;176 VAC ± 3 % at 100% Load;Low Line Comeback: Low Line Loss Voltage + 10V;High Line Loss: 300 VAC ± 3 %;High Line Comeback: High Line Loss Voltage - 10V;Frequency Range: 46Hz ~ 54 Hz @ 50Hz system, 56Hz ~ 64 Hz @ 60Hz system;Phase: Single phase with ground;Power Factor: ≧ 0.99 at 100% Load | |
Output | Output voltage: 208/220/230/240VAC;AC Voltage Regulation: ± 1%;Frequency Range (Synchronized Range): 46Hz ~ 54 Hz @ 50Hz system, 56Hz ~ 64 Hz @ 60Hz system;Frequency Range (Batt. Mode): 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz;Overload:;AC mode: 100%~110%: 30min; 110%~130%: 5min; >130% : 10sec;Battery mode: 100%~110%: 3min; 110%~130%: 30sec; >130% : 10sec;Current Crest Ratio: 3:1 max;Harmonic Distortion: ≦ 3 % THD (Linear Load), ≦ 5 % THD (Non-linear Load) | |
Battery | Standard Model:;Battery Type: 12 V / 9 Ah;Numbers: 16;Recharge Time: 9 hours recover to 90% capacity;Charging Current: Default : 1 A ± 10%, Max.: 1A, 2A (Adjustable);Charging Voltage: 218.4V ± 1%;Long-run Model:;Battery Type: Depending on applications;Numbers: 16-20;Charging Current: Default: 4 A ± 10%, Max.: 1A, 2A, 4A, 6A (Adjustable, 6A is only available for 16pcs batteries);Charging Voltage: 218.4V ± 1% (based on 16pcs batteries) | |
Environment | Operation Temperature: 0 ~ 50°C (battery life cycle will be shorten when temperature is above 25°C);Operation Humidity: < 95 % and non-condensing;Operation Altitude**: <1000m;Acoustic Noise Level: Less than 55dB @ 1 Meter | |
Dimensions | 369 x 190 x 688mm |